A6 series inverter
1. A6 series is a high performance vector/torque control inverter, G type is constant torque/heavy load, overload capacity is 150% 1 minute, L type is variable torque/light load, overload capacity is 115% 1 minute.
2. The standard built-in brake unit is less than 15K, 18.5-45 kW/55–7kW. If additional built-in brake units are required, please specify when ordering.
Characteristic performance: |
Revolving speed tracking start | The frequency converter recognizes the speed of the rotating motor and directly tracks the start from the identified frequency. The current and voltage in the starting process are smooth and no-impact |
Low frequency high torque | Closed loop vector control 0.00Hz 180%; Open loop vector control 2:0.25Hz 180% ; Open loop vector control 1: 0.50Hz 180% |
Key functions | Torque/speed control mode switching, multi-function input/output terminals, undervoltage regulation, three-way switching, revolving speed tracking,torque limit, multi-speed operation (up to 23 sections), auto-tuning, S-curve acceleration/deceleration slip compensation, PID adjustment, droop control, current limit control, manual/automatic torque boost, current limit |
Frequency range | 0 . 00~300 . 00 H z Note: Open loop vector control 1 mode 0 . 0 ~ 3000 . 0 H z can be customized according to customer needs |
Starting frequency | 0. 00~60. 00Hz |
Acceleration and deceleration time | 0. 1 ~ 36000s. (A4 above supports 0.01s) |
Energy consumption braking capacity | Braking unit operating voltage: 650 to 750V |
DC braking capability | DC braking starting frequency: 0. 00 ~ 300. 00Hz. DC braking current: constant torque 0. 0 ~ 120. 0%; variable torque 0. 0 ~ 90. 0% DC braking time: 0. 0~30. 0s: No need of DC brake start waiting time for quick braking |
Flux brake function | Continuing operating, no operating is optional during deceleration, factory default does not operate during deceleration |
Copy of parameters | The standard operation panel can realize parameter uploading and downloading with a copy progress indication; the uploaded parameters can be selected to be prohibited from being uploaded and overwritten. |
Common DC bus | Full series can realize multiple frequency converters sharing DC bus power supply |
Independent duct | The whole series adopts independent air duct design to support the ambient installation mode of radiator |
Universal expansion interface | Support customers for secondary development of universal expansion board with CPU: Physical interface SPI bus, software protocol Mod bus |
Expansion card | PG feedback card, constant pressure water supply module, Modbus, Profibus, Can communication adapter |
Power on self- inspection | Achieve power-on self-inspection of internal and external circuits, such as motor grounding, +10 V power output abnormality, analog input abnormality, and disconnection. |
Special protection | Undervoltage, overcurrent protection, overvoltage protection, interference protection, auto-tuning fault, module protection, radiator overheat protection, frequency converter overload protection, motor overload protection, peripheral protection, abnormal current detection, abnormal output short circuit current to earth, abnormal power off during operation, input power supply abnormality, output phase loss abnormality, EEPROM abnormality, relay pull-in abnormality, temperature sampling disconnection, encoder disconnection, +10 V power output abnormality, analog input abnormality, motor overheat (PTC), communication abnormality, version compatibility abnormalit y, copy abnormality, expansion card connection abnormality, terminal mutex check failed, hardware overload protection |
A6Series frequency converter adaptor motor list |
Power (kW) | 0.75 | 1.5 | 2.2 | 3.7 | 5.5 | 7.5 | 11 | 15 | 18.5 | 22 | 30 | 37 | 45 | 55 |
Motor power (kW) | 0.75 | 1.5 | 2.2 | 3.7 | 5.5 | 7.5 | 11 | 15 | 18.5 | 22 | 30 | 37 | 45 | 55 |
Output | Voltage (V) | 3 Phase 0- Rated AC input voltage | 3 Phase 0- Rated AC input voltage | 3 Phase 0- Rated AC input voltage | ||||||||||||
Rated current(A) | 2.5 | 3.8 | 5.5 | 9 | 13 | 17 | 24 | 30 | 39 | 45 | 60 | 75 | 91 | 112 | ||
Overload capacity | 150% 1 minute, 180% 10 seconds, 200% 0.5 seconds, interval 10 minutes (inverse time limit characteristi c) |
Input | Rated voltage/frequency | Three-phase 380V-480V; 50Hz/60Hz | Three-phase 380V-480V; 50Hz/60Hz | Three-phase 380V-480V; 50Hz/60Hz | ||||||||||||
Allowable range | 323V -528V, voltage unbalance degree: ≤ 3%, allowable frequency fluctuation: ±5% | |||||||||||||||
Rated current(A) | 3.5 | 6.2 | 9.2 | 14.9 | 21.5 | 27.9 | 39 | 50.3 | 60 | 69.3 | 86 | 104 | 124 | 150 |
Braking unit | Standard built-in | Standard built-in | Standard built-in | Standard built-in | Built-in optional | Built-in optional | Built-in optional |
Protection class | IP20 | IP20 | IP20 | IP20 | IP20 | IP20 | IP20 | IP20 | IP20 | IP20 | IP20 | IP20 | IP20 | IP20 |
Cooling method | Self-cooling | Forced air cooling | Forced air cooling | Forced air cooling | Forced air cooling | Forced air cooling | Forced air cooling |
Power (kW) | 75 | 90 | 110 | 132 | 160 | 185 | 200 | 220 | 280 | 315 | 355 | 400 | 450 | 800 |
Motor power (kW) | 75 | 90 | 110 | 132 | 160 | 185 | 200 | 220 | 280 | 315 | 355 | 400 | 450 | 800 |
Output | Voltage (V) | 3 Phase 0- Rated AC input voltage | 3 Phase 0- Rated AC input voltage | 3 Phase 0- Rated AC input voltage | ||||||||||||
Rated current(A) | 150 | 176 | 5.5 | 9 | 13 | 17 | 24 | 30 | 39 | 45 | 60 | 75 | 91 | 112 | ||
Overload capacity | 150% 1 minute, 180% 10 seconds, 200% 0.5 seconds, interval 10 minutes (inverse time limit characteristi c) |
Input | Rated voltage/frequency | Three-phase 380V-480V; 50Hz/60Hz | Three-phase 380V-480V; 50Hz/60Hz | Three-phase 380V-480V; 50Hz/60Hz | ||||||||||||
Allowable range | 323V -528V, voltage unbalance degree: ≤ 3%, allowable frequency fluctuation: ±5% | |||||||||||||||
Rated current(A) | 201 | 160 | 9.2 | 14.9 | 21.5 | 27.9 | 39 | 50.3 | 60 | 69.3 | 86 | 104 | 124 | 150 |
Braking unit | Built-in optional | External braking unit required | External braking unit required | External braking unit required |
Protection class | IP20 | IP20 | IP20 | IP20 | IP20 | IP20 | IP20 | IP20 | IP20 | IP20 | IP20 | IP20 | IP20 | IP20 |
Cooling method | Forced air cooling | Forced air cooling | Forced air cooling | Forced air cooling | Forced air cooling | Forced air cooling | Forced air cooling |